Water source and Water quality improvement project of Houwo Reservoir

The project is including advanced processing such as Fiber Filter (MF), Ultra Filtration (UF), and Reverse Osmosis (RO).

The main purpose is to improve water qualities such as Chloride and Total dissolved solied which are difficult to be removed in traditional water purification procedures, and further improvse the quality of drinking water for local residents & tourists.

After 15 consecutive days of functional tests: Chloride ≤ 50 mg/L(drinking water quality standard is 250 mg/L), Total dissolved Solids ≤ 120 mg/L(drinking water quality standard is 500 mg/L), are all better than Taiwan's drinking water quality standards.